Although no building or component can provide fail-safe protection, buildings can play an important role in the defense against terrorist attacks, even when the weapons used are chemical, biological or radiological (CBR). One element of the building that is receiving more security scrutiny than it did in the past is the HVAC system. The ventilation system and air filtration — along with building architecture and security hardware and procedures — can help reduce the likelihood of loss of life and mass contamination of the facility.

Before any steps are taken, a risk assessment should be conducted identify threats to and vulnerabilities. If the analysis shows a need for action to protect the building and its occupants against a CBR attack, the facility executive should not overlook the importance of the HVAC system.

One important step is to program controls to allow ventilation systems to be placed in the appropriate mode from a single switch. Multiple devices may well have to be de-energized in an emergency, often at different locations. It is not reasonable to think an operator can control all these devices individually under emergency conditions.

Ventilation strategies will depend on whether the CBR release occurs inside or outside the building. If there are no visible signs of an outdoor release, and if some areas of the building appear to be more severely affected than others, then the assumption should be made that the release was indoors. A biological or radiological agent will almost never cause immediate symptoms, while a chemical agent almost always will.

If the release is outside, supply fans must be shut off unless the HVAC system is equipped with an appropriate filtration system; if the system does have a high-performance filtration system as described below, supply fans should be kept running. Exhaust fans should be shut off, fresh air intakes and building envelope openings closed, elevators recalled to the lobby, and all doors locked, including those to the loading dock and garage. Occupants should remain indoors, preferably in the interior of the building.

It’s a different story if a release occurs inside the building. Closing duct dampers, where possible, will help isolate the zone of release. The stairwell pressurization system should be activated using 100 percent outside air as occupants are evacuated to a predetermined location.

Type Of Release
Different measures are called for depending on whether the release involves biological, radiological or chemical agents. For a chemical release, the goal is to reduce the concentration to which people are exposed. The best strategy is to provide 100 percent outdoor air to areas surrounding the floor or area of release while providing 100 percent exhaust only to the floor or area of release. If that is not possible, the next best approach is to provide the entire area with 100 percent outdoor air and 100 percent exhaust. If that is not possible, all supply and return fans should be shut down until the type of hazard and extent of spread is determined. Once this information is known, consideration should be given to reactivating the HVAC system. In most buildings the normal operation of the system will provide some outdoor air and will exhaust some indoor air, providing a beneficial diluting effect.

For a biological or radiological release, the goal is to minimize the number of people exposed. That means shutting down all supply, return and exhaust fans. Fans should not be restarted, under any circumstances, unless directed by a competent authority.

In the case of a biological release, segregate people known to be exposed to avoid cross-contamination.

For ordinary operation, non-public areas should have a slightly positive pressure with respect to public areas and the outdoors. This will minimize air infiltration from any external release. In ductwork distribution zoning, consider separating zoning (and air flow paths between zones) to reduce the number of people exposed to an internal release. Large central systems can quickly spread contaminants; more decentralized systems would be preferred in high-risk facilities.

The ventilation system should be designed to isolate entry and storage zones, such as the lobby, mailroom and receiving areas. These are locations where there is the greatest risk of entry and where screening can be done in high-risk buildings. Full-height walls are advisable, as is sealing all openings as would be required for a smoke barrier. Separate air handlers will isolate these areas from the rest of the building. The supply and return ducts entering each public lobby, other unsecured public areas, and mailrooms should have quick-closing isolation dampers, which could be manually activated by a 24/7 manned guard booth located at each entry. Dedicated exhaust systems should serve each public area. These areas should be maintained at a slight negative pressure to the remainder of the building. In high-traffic areas, airlocks or vestibules are worth considering.

Air Filtration
Air filtration can provide an additional line of defense against a CBR release. The filter bank can be installed in series with the main air handling unit for continuous filtration or in a bypass configuration for switched-in CBR filtration. After the risk assessment establishes the required protection and associated range of efficiencies, a comparison of the many styles and configurations should be based upon a complete life cycle cost analysis. Will improved IAQ justify the upgrade and operating costs? Can the maintenance be sustained in terms of personnel training and material cost? How will hazardous waste be disposed of? It will become obvious from the analysis that energy overwhelms all other cost factors, including first cost.

Analyzing Choices
There are several major types of filters with performances suitable for CBR filtration. The first are HEPA filters. These filters are 99.97 percent efficient in capturing 0.3 micron diameter particles; improvements in media manufacturing have resulted in even higher efficiencies.

Most known bacteria range in size from 0.2 to 5 microns in diameter. Viruses are between 0.01 and 0.3 microns. However, viruses need a host to live and therefore usually are attached to a bacteria or other large object such as a water droplet (0.5 to 5 microns).

The addition of building-wide HEPA filters carry an extremely high construction, maintenance, and operating cost, particularly in a retrofit situation. Even in cases where the costs cannot be justified for the entire building, however, it may be worth installing HEPA filters in the ductwork of the stairway emergency ventilation system if the intake is at low level. The higher grade of filtration can be justified because of the critical nature of stairs and the concentration of people in a confined area when it is used as the emergency egress. Anthrax spores are difficult to clean on a large scale, such as a stairway. A week or multi-week shutdown of stairways would virtually take the entire building off-line.

High-efficiency filters — those with minimum efficiency reporting value (MERV) ratings of 14, 15 or 16 on a scale of 1 to 20 — can also be considered for defense against biological attacks. The higher the MERV number designation, the better the capture efficiency, particularly at the smaller sizes. Their filtration efficiency, ranging from 90 percent to 99 percent for anthrax bacteria (1 micron) and nearly 100 percent in the spore state (2 microns) is fairly similar to a HEPA filter (99.97 percent at 1 micron). However, for smaller pathogenic bacteria and water-droplet-carrying viruses that are between 0.2 and 0.5 microns, their efficiency drops to the range of 60 percent to 95 percent. These filters would not guard against chemical gas attack.

High-efficiency filters represent a cost-effective alternative to HEPA filters when very high filtration of particles smaller than 1 micron is not required. They cost less, impose less air pressure demand on the fan motor and tend to require less retrofit work to an existing air handling system.

A third category of filtration that can be considered for defense against the toxic gases that terrorists might use is activated carbon. Activated carbon adsorbs, not absorbs, airborne odors and vapors. When a material adsorbs something, it means that it attaches to it by chemical attraction.

Activated carbon adsorbs to its own surface. When there are no more surfaces left, activated carbon is depleted of its effectiveness. Large amounts of carbon will last longer than small amounts. The thicker the carbon filters, the better its adsorption. Granular-activated carbon is more effective than a 1- or 2-inch thick impregnated carbon pad. The performance of activated carbon is affected by temperature and humidity, contaminant chemistry and concentration.

Activated carbon can be impregnated with chemicals to make it a more effective adsorbent. The broad-based chemical ASZM-TEDA (copper, silver, zinc and molybdenum-triethylenediamine) is currently considered by the Defense Department and the Homeland Security Department to be the most effective collective filtration for industrialized and militarized chemicals, when used in conjunction with an adequate residence time across the carbon bed (i.e., the amount of time the activated carbon is in contact with a pollutant).

Like HEPA filters, activated carbon filters have very high construction, maintenance and operating costs, especially in existing buildings. What’s more, careful coordination between the architectural room plan and structural floor supports is required for carbon filters and housing because of their weight.

Other Filtration Technologies
Although low- and medium-efficiency filters with an antimicrobial agent are available, there is not sufficient consensus in the industry to recommend these filters for anywhere but residential applications. Direct contact is required for an antimicrobial agent to destroy microorganisms, and dust build-up will tend to inhibit direct contact. There is no evidence that microorganisms that lodge downstream within the filter media are inhibited or killed.

One type of ultraviolet light, UV-C, has been used as a germicide in health care, food processing and waste treatment for more than 50 years. However, because numerous variables affect the killing ability of UV-C emitters — including air temperature, humidity and tube cleanliness — it is recommended that for purposes of bioterrorist defense, the UV-C emitter only be considered as a supplement to air filters.

At least one manufacturer offers a hybrid filtration system that consists of a low wattage electrostatic air cleaner with a UV-C emitter installed upstream. The filtration efficiency is about 95 percent for 1-micron particles; however, efficiency drops to 75 percent for 0.5-micron particles and to 33 percent for 0.3-micron particles.

Most of the options considered for building infrastructure enhancement apply to both new and existing structures. With existing buildings, however, the economic realities of renovations may limit choices.

Terry Gillick is vice president, security technology, Syska Hennessy Group, New York City. The firm provides consulting, engineering, technology and construction services in such areas as building system design, facilities management, energy management, security technology consulting/engineering and turnkey design/build.